General Specification |
Auto Reset Models Manual Reset Models* |
20 20M |
20-L 20-LM |
20-H 20-HM |
Operating Voltage |
190-480 VAC |
95-120 VAC |
475-600 VAC |
Power Consumption |
3.7W at 480V |
3.7W at 120V |
4.5W at 600V |
Auto Ranges |
Yes |
No |
Frequency |
50/60Hz |
Type of Measurement |
RMS |
Under Voltage Trip Reset |
(% of setpoint) 90% ±1% 93% ±1% |
Over Voltage Trip Reset |
(% of setpoint) 110% ±1% 107% ±1% |
Voltage Unbalance Trip Reset |
(conforms to NEMA) 2-8%, adjustable Trip setting minus 0.7% |
Trip Delay Time Over, Under, & Unbalanced Single-Phasing Faults Unbalance > 15% |
1-30 sec., adjustable 1 sec., fixed 1 sec., fixed |
Restart Delay |
1-500 sec., adjustable |
Manual Reset Input |
5V open circuit/500µA short circuit |
Output Contacts |
SPDT 10 amps at 240VAC resistive |
Operating Temp |
- 20º to +140º F |
Humidity Tolerance |
0-97% w/o condensation |
Terminal Torque |
3.5 in. lbs. maximum |
Wire Type |
Stranded or solid 14-26 AWG, 1/terminal |
Enclosure |
Noryl plastic |
Mounting |
DIN Rail or Surface Mount |
Weight |
11 oz. |
Option for Low Current Applications |
Models ordered with suffix "/SG" have silver with gold flash contacts |
Agency Approval |
UL Recognized (U.S. and Canada) (For use in a Pollution Degree 2 Environment) |